Product Selection:
Technical Parameters:
|
Type |
AOH-125 |
|
Standard |
GB14048.3、IEC60947-3 |
|
Pole |
1、2、3、4 |
|
Rated Current(A) |
25、40、63、80、100、125 |
|
Rated Voltage(V) |
AC230(1P)、AC230/400 |
|
Insulation Voltage |
690 |
|
Rated Impulse Withstand Voltage(KV) |
6 |
|
Rated Short-Circuit with Stand Current |
12le/1s |
|
Rated Short-Circuit Making Capacity |
4.5KA |
|
Rated Making and Breaking Capacity |
4.5KA |
|
Utilization |
AC-21B、AC-22A |
|
Electrical Life |
1500 |
|
Mechanical Life |
8500 |
|
Pollution Grade |
2 |
|
Protection Level |
IP20 |
|
Temperature |
-35℃~ +70℃ |
|
Altitude |
Do not Exceed 2000m |
|
Wiring Terminal |
Screw Crimping |
|
Max. Connection Capacity (m㎡) |
16(20A~63A) 50(80A~125A) |
|
Max.Ultimate Torque (Nm) |
2.0(20A~63A) 3.5(80A~125A)
|
|
Installation Category |
II、III |
|
Installation Method |
TH35-7.5 Standard DIN rail |
|
lncoming Wiring Method |
Can Be Installed Up or Down |
|
lnstallable Accessories |
- |
Outline Overall and Installation Dimensions (mm):